1. Hot water coils offer fully modulating control through the use of a 3 way valve. The hot water coil, connections and valves are all tested at pressure of 15 bars. Frost protection is provided by forcing the opening the 3 way valve when supply temperature from hot water coil falls below 8°C and by stopping the outdoor fan when that supply temperature falls below 6°C. In addition to that, the 3 way valve is also opened at 10% value if the outdoor temperature falls below an adjustable value.
2. Hot water coils are always factory fi tted, wired and fully tested, prior to shipment.