Model No.: RTU12~RTU300
Brand: Amrta or OEM
Type: Air-Cooled
Cooling Method: Air-cooled
Unit Structure: Integral
Selected Voltage: 380V/50HZ
Noise Level: Ordinary
Certification: CE
Condition: New
Explosion-proof: Optional
Application Fields: Mechanical Engineering, School, Airport, Shopping Mall, Industrial Buildings
Refrigerant: R410A/R407c/R134A/R22
Compressor: Danfoss/Copeland/Panasonic/Daikin
Cooling Capacity: 12kw-300kw
Electric Parts: Schneider Brand
Refrigerant Valves: Danfoss/Emerson Brand
Controller: Syslab Brand Or Siemens PLC(optional)
Power Supply: 380~415V, 440~460V, 50HZ/60HZ
Unit Type: Cooling Only/Heat Pump/Cooling Only With Electric Heater
Packaging: Plywood Casing or standard package suitable for sea and air transport
Productivity: 6000PCS/Year
Transportation: Ocean,Air
Place of Origin: China
Supply Ability: 500PCS/Month
HS Code: 8418612090
Port: Qingdao,Shandong,China
Payment Type: L/C,T/T,Western Union
Incoterm: FOB,CFR,CIF
When it comes to your comfort, you don`t want to take more time to choose the Air Conditioner. That`s why so many before you have turned to the experts at Amrta Air Conditioner for indoor comfort innovation and reliability. When you choose Amrta HVAC System, you can be confident that your new system is designed, built and backed by the world`s foremost comfort innovator. In addition, AMRTA products undergo one of the most rigorous quality control regimens in the industry. From performance and quality testing during product development to our 100% run testing during production, we don`t miss an opportunity to meet the toughest requirements of our partners
● Industrial buildings and logistic centers
● Wide choice of communication interfaces
Technical Data
Model | RTU45 | RTU50 | RTU60 | RTU75 | RTU90 | RTU105 | ||
Cooling capacity | kW | 44.5 | 50 | 60 | 70 | 90 | 105 | |
Heating capacity | kW | 48.7 | 54.3 | 64 | 75.4 | 96.2 | 113.2 | |
Power supply | 380V / 3Ph / 50HZA | |||||||
Cooling power input | kW | 17 | 19.5 | 22.8 | 26.7 | 32.9 | 39.7 | |
Heating power input | kW | 15.6 | 18 | 21 | 24.8 | 30.4 | 36.7 | |
Start current | A | 168 | 186 | 175 | 199 | 197 | 266 | |
Working current in cooling | A | 31.7 | 35.6 | 39.9 | 48.3 | 61 | 70.6 | |
Working current in heating | A | 29.9 | 33.5 | 37.5 | 45.4 | 57.3 | 66.3 | |
Throttle methods | Thermal expansion valve | |||||||
Circuits | 2 | 2 | 2 | 2 | 3 | 3 | ||
Refrigerant | R410A | |||||||
Compressor | Type | Scroll type 380V / 3Ph / 50HZA | ||||||
Qty | 2 | 2 | 2 | 2 | 3 | 3 | ||
Condenser side | ||||||||
Condenser | Type | Al+copper tube | ||||||
Axial fan | Qty | 1 | 1 | 1 | 1 | 2 | 2 | |
Drive | Direct drive | |||||||
Motor power | kW | 0.25 | 0.37 | 0.37 | 0.55 | 0.75 | 0.75 | |
Air flow | m3 /h | 4600 | 7800 | 7800 | 9000 | 12600 | 12600 | |
Evaporator side | ||||||||
Evaporator | Type | Al+copper tube | ||||||
Centrifugal fan | Qty | 1 | 1 | 1 | 1 | 1 | 1 | |
Motor power | kW | 3 | 3 | 4 | 4 | 5.5 | 5.5 | |
Air flow | m3 /h | 7600 | 8500 | 10900 | 12500 | 16000 | 19500 | |
Drive | Direct drive | Belt drive | ||||||
External static pressure(Pa) | 250 | 250 | 300 | 300 | 300 | 300 | ||
Filter | Aluminum frame filter G3 | |||||||
Noise level dB(A) | 73 | 73 | 73 | 75 | 74 | 75 | ||
Dimension | L | mm | 2268 | 2268 | 2298 | 2298 | 2878 | 2878 |
W | mm | 1440 | 1440 | 1650 | 1650 | 2140 | 2270 | |
H | mm | 1167 | 1167 | 1400 | 1400 | 1964 | 1964 | |
Weight | kg | 750 | 770 | 830 | 860 | 1160 | 1350 |
* Performance values refer to the following conditions:
Cooling: room air temperature 27.0°C DB RH 50%, ambient air temperature 35°C;
Heating: room air temperature 20.0°C DB, ambient air temperature 7°C DB / 6°C WB.
** Noise level measured by adopting average value in the noise lab with background noise of 25 dB(A), at a distance of 1.5m high fan speed.
Installation
Product Categories : Rooftop Packaged Unit > Explosion Proof Rooftop Packaged