Model No.: RTU12~RTU300
Brand: Amrta or OEM
Type: Evaporative Air Cooler
Air Tube Material: Galvanized Sheet
Corrosion Durability: General
Operating Voltage: 380/400 VAC
Noise Level: Low
Mounting: Floor Standing
Lifetime: 15~20 years
Certification: CE
Condition: New
Application Fields: Mechanical Engineering, School, Airport, Shopping Mall, Industrial Buildings
Refrigerant: R410A/R407c/R134A/R22
Compressor: Danfoss/Copeland/Panasonic/Daikin
Cooling Capacity: 12kw-300kw
Electric Parts: Schneider Brand
Power Supply: 380~415V, 440~460V, 50HZ/60HZ
Refrigerant Valves: Emerson/Danfoss Brand
Controller: Syslab(standard), Siemens PLC(Optional)
Optional: Energy Recovery,
Energy Recovery Type: Plate Type Or Wheel Type
Packaging: Plywood Casing or standard package suitable for sea and air transport
Productivity: 5000PCS/Year
Transportation: Ocean
Place of Origin: China
Supply Ability: 400PCS / Month
HS Code: 8418612090
Port: Qingdao,Shandong,China
Payment Type: L/C,T/T,Western Union
Incoterm: FOB,CFR,CIF
Amrta Rooftop Packaged Unit provide the solution to building managers and engineers, warehouses and industrial applications. Energy recovery and Free Cooling is optional, for Rooftop Packaged Unit with Free Cooling. Free cooling with 100% fresh air possible have the advantages: Improved air quality; Energy saving using fresh outdoor air to cool the building. Standard CO2 sensor connection Ideal balance between efficiency and indoor air quality. Includes all base model features. 3 damper version,
with integrated fresh air and extraction
● Industrial buildings and logistic centers
● Wide choice of communication interfaces
G4 filter, plate and bag filter
The HR system is now widely applied in residential, commercial, industrial applications. Practically, applications which demand the higher quality air and fresh air rate are strongly recommended.
Plate heat recovery
① Fresh air ② Return air ③ Supply air ④ Exhaust air
Wheel heat recovery
① Fresh air ② Return air ③ Supply air ④ Exhaust air
Technical Data
Model | RTU45 | RTU50 | RTU60 | RTU75 | RTU90 | RTU105 | ||
Cooling capacity | kW | 44.5 | 50 | 60 | 70 | 90 | 105 | |
Heating capacity | kW | 48.7 | 54.3 | 64 | 75.4 | 96.2 | 113.2 | |
Power supply | 380V / 3Ph / 50HZA | |||||||
Cooling power input | kW | 17 | 19.5 | 22.8 | 26.7 | 32.9 | 39.7 | |
Heating power input | kW | 15.6 | 18 | 21 | 24.8 | 30.4 | 36.7 | |
Start current | A | 168 | 186 | 175 | 199 | 197 | 266 | |
Working current in cooling | A | 31.7 | 35.6 | 39.9 | 48.3 | 61 | 70.6 | |
Working current in heating | A | 29.9 | 33.5 | 37.5 | 45.4 | 57.3 | 66.3 | |
Throttle methods | Thermal expansion valve | |||||||
Circuits | 2 | 2 | 2 | 2 | 3 | 3 | ||
Refrigerant | R410A | |||||||
Compressor | Type | Scroll type 380V / 3Ph / 50HZA | ||||||
Qty | 2 | 2 | 2 | 2 | 3 | 3 | ||
Condenser side | ||||||||
Condenser | Type | Al+copper tube | ||||||
Axial fan | Qty | 1 | 1 | 1 | 1 | 2 | 2 | |
Drive | Direct drive | |||||||
Motor power | kW | 0.25 | 0.37 | 0.37 | 0.55 | 0.75 | 0.75 | |
Air flow | m3 /h | 4600 | 7800 | 7800 | 9000 | 12600 | 12600 | |
Evaporator side | ||||||||
Evaporator | Type | Al+copper tube | ||||||
Centrifugal fan | Qty | 1 | 1 | 1 | 1 | 1 | 1 | |
Motor power | kW | 3 | 3 | 4 | 4 | 5.5 | 5.5 | |
Air flow | m3 /h | 7600 | 8500 | 10900 | 12500 | 16000 | 19500 | |
Drive | Direct drive | Belt drive | ||||||
External static pressure(Pa) | 250 | 250 | 300 | 300 | 300 | 300 | ||
Filter | Aluminum frame filter G3 | |||||||
Noise level dB(A) | 73 | 73 | 73 | 75 | 74 | 75 | ||
Dimension | L | mm | 2268 | 2268 | 2298 | 2298 | 2878 | 2878 |
W | mm | 1440 | 1440 | 1650 | 1650 | 2140 | 2270 | |
H | mm | 1167 | 1167 | 1400 | 1400 | 1964 | 1964 | |
Weight | kg | 750 | 770 | 830 | 860 | 1160 | 1350 |
* Performance values refer to the following conditions:
Cooling: room air temperature 27.0°C DB RH 50%, ambient air temperature 35°C;
Heating: room air temperature 20.0°C DB, ambient air temperature 7°C DB / 6°C WB.
** Noise level measured by adopting average value in the noise lab with background noise of 25 dB(A), at a distance of 1.5m high fan speed.
Product Categories : Rooftop Packaged Unit > Energy Recovery Rooftop Packaged